Routine Test
- Inspection of assembly including wiring
- Continuity Test
- Insulation Resistance tested by (Megger) 500/1000 V
- High Voltage Test by HV Test Kit 2 kV for 1 minute
Type Test
- Short cicuit test as per IS 8623 (part I) 8.2.3-1993
- Temperature rise test as per IS 8623 (part I) 8.2.1 -1993
Special Test
- Primary injection test
- Secondary injection test
- Verification of Power Coat thickness